Table Of Contents

Title:

Piping and Valves

Doc. No.

L-001

Annex

F

VSK

V408

Project: NORSOK

Company:

Rev.Date:

 15.12.97

Rev:

2

 

Text

ID

DATE

VSK. TEXTS

600

20.06.94

These valves have low temperature properties for services operating for a limiting periode of time at the low temperature, e.g. blowdown. Continous cryogenic service would normally require valve with bonnet extension for stem sealing.

 

15.12.97

If temperature is between -47oC and -101oC for a limiting period of time, e.g. blowdown, the valves shall not be operated in this temperature range.